Powador- protectOperating InstructionsnEnglish translation of German original
Page AAmbient temperature range [°C]-20 ... +70Maximum installation elevation (m above mean sea level)2000Protection rating accord-ing to EN 60529I
Page Af< 47.5 Hz 100 msCountry setting "IT-CEI021"Setting range Default valuesValue Time Value TimeU> 1...1.2 Unom0.2...10 s 1.1 Uno
Page ACountry set-ting "User dened"Setting range Default valuesValue Time Value TimeU> 1...1.25 Unom100...60000 ms 1.15 Unom100 msUR&g
Page AScope of delivery• x Powador-protect• x jumpers for bus termination• x cable set for AC connection• x ferrite clip• Documentation
Page ARequirements for the installation space• Contact protection for the device and connection leads must be ensured• Installation in the immedia
Page AI IIIIIFigure 1: Top hat rail mounting. Mounting the device onto a wall ↻ Mount the device in the immediate vicinity of the feed-in meter.
Page A Device overview2122141112NL3L2L1A2A1RS485B RS485A GND RS485B RS485A GND CAN H CAN L GND CAN H CAN L GNDD01GN
Page AConnector strip on the upper side of the housingElectrical connections DescriptionA A1, A2 Connection terminals for AC power supplyB L1, L2,
Page A Electrical connectionMake the electrical connection via the screw terminals on the top of the device. Use a slot screwdriver (max. blade wi
Page ANOTEGrid failure bridging timeWith a supply voltage of V to < V, the grid failure bridging time is ms.With a supply voltage drop
Page A. AC connectionDANGERRisk of fatal injury due to electric shockSevere injury or death will result if the live connections are touched. › Be
Page A. Connect neutral conductor N to screw terminal A. Connect the stripped wire end of the jumper and the AC supply line to screw terminal A
Page A ↻ Make AC connection. Use suitable fuses!� Connect AC measuring lines (L, L, L) and neutral conduc-tor N to the relevant screw terminals
Page ASupply Contact load capacity on the Powador-protectAC 250 V / 2 A inductiveDC 24 V / 8 AConnect AC supplied tie circuit-breaker (Figure ) ↻ Y
Page AConnecting the DC-supplied tie circuit-breaker (Figure ) ↻ You have installed suitable external tie circuit-breakers between feed-in meter
Page AConnecting the ripple control receiver to the Powador-protect ↻ You have correctly tted and installed the ripple control receiver. ↻ Note the
Page A2122141112NL3L2L1A2A1D01GNDDI4DI3DI2DI12421L1L2L3NL1L2L3NFigure 10: AC tie circuit-breaker; signal sources for remote shutdown and frequency
Page A.. Connect feedback contact of the tie circuit-breakerto monitor the triggering of the tie circuit-breaker.Country setting: "IT-CEI
Page A. Digital output "inverter o"Country settings: "Germany", "IT-CEI", "User Dened"Output signal
Page A. RS busNOTEEnsure that the DATA+ and DATA- wires are properly connected. Communication is not possible if the wires are reversed.NOTEDi
Page AContents General Information ... Safety ...
Page A.. Connecting the RS busNOTE� To prevent interference during data transmission:• Observe the wire twisted pairing when connecting DAT
Page A.. Activate connection resistance (optional)Activate the terminating resistor if the Powador-protect represents the terminal unit within y
Page A Starting up the Powador-protect. Switching on Powador-protect ↻ The device has been mounted and electrically installed.. Connect the A
A Text displayThe text display shows measured values and data and allows the buttons, the backlighting is activated. If no button is pressed for a c
Page AOperating status LEDs DescriptionWait for connectionThe device monitors the grid and con-nects the PV system according to the waiting time set
Page AMenu level » Menu level is active by default and displays settings and status messages.Open menu level ↻ Menu level must be active.�
Page ASave settings and exit menu (menu levels and only)� Press Action and Forward buttons simultaneously.. Menu structureIcons used:Displ
Page AMenu level Shows measurements, country setting, software version and recorded events. Each menu option is displayed for seconds. After a co
Page ADisplay Action in this menu/meaningRS485 role Set role of the Powador-protect in the RS busMaster: no proLOG is used, Powador-protect is t
Page ADisplay Action in this menu/meaningF<: val, ToLimit value frequency drop protector and trig-ger delay time for level /level shutdownF&l
Page A General Information. About this documentWARNINGImproper handling of the device can be hazardousYou must read and understand the operating
Page AMenu level Display and change of critical system settings. Observe the grid operator guidelines. Non-compliance may result in the operating
Page ADisplay Action in this menu/meaning2-stage paramsEnable: Permit setting of the shutdown limits for shut-down level Disable: Prohibit settin
Page ADisplay Action in this menu/meaningTstartTime of grid monitoring up to connection after device restart (in s)TwaitTime of grid monitoring up
Page A Maintenance/Troubleshooting. Visual inspectionInspect the device and the cables for visible external damage and note the operating sta
Page A. TroubleshootingFault Cause RecticationThe display is blank and the LEDs are not lighting up. ↻ Grid voltage not available.� Check whet
Page A. Status and fault signalsOn the device, the last recorded fault or operating status mes-sages (Log ... Log ) with date and time of
Page ALine errorDisplay Fault descriptionLNx_U10M>Shutdown due to excedance of the voltage increase protector level /level on phase x (-minu
Page A Warranty and Service. Factory warranty and liabilityOn our website http://www.kaco-newenergy.de/ you will nd our latest warranty cond
Page AKACO new energy GmbH will only perform warranty services if the defective unit is returned to KACO new energy GmbH together with a copy of the
Page A EU Declaration of ConformityVendor’s name and addressKACO new energy GmbH Carl-Zeiss-Straße Neckarsulm, GermanyProduct descriptio
Page ASafety warnings symbols guideDANGERHigh risk Failure to observe this warning will lead directly to serious bodily injury or death.WARNINGPotent
Page AThe product mentioned above is therefore labelled with the CE marking.Unauthorised modications to the supplied units and/or any use of the un
Page A
Carl-Zeiss-Straße 1 74172 Neckarsulm Germany Tel. +49 7132 3818-0 Fax +49 7132 3818-703info@kaco-newenergy.dewww.kaco-newenergy.de3008096-01-140408
Page A Safety. Proper useThe Powador-protect is correctly used• to monitor undervoltage, overvoltage, underfrequency and over-frequency – in a
Page ADANGERRisk of fatal injury due to electric shock › Observe all safety regulations and the current technical connection specications from the r
Page A Technical Data. Electrical dataSupplyVoltage supply [VAC] 100 ... 264Nominal voltage Unom [VAC] 230Max. power consumption [W] 2.5Measurem
Page A. Mechanical dataInterfacesMeasurement Screw terminals 4-pin (L1/L2/L3/N)Switch contacts2 changeover contacts for connecting external tie c