Maintenance/Troubleshooting
Page  Operating Instructions Powador . TL-. TL
. Messages on the display and the “Fault” LED
Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The triggering levels are
dened in standards, e.g. VDE--. The inverter shuts down if the values exceed or fall below the approved levels.
.. Display of status and fault messages
Display Fault LED (red)
FS (fault status) ON
Fault signal relay has switched.
Feed-in was ended due to a fault.
OS (operating status)
OFF
The fault signal relay releases again.
The inverter feeds back into the grid again after
acountry-specic time period.
Details regarding the fault or operating status can be found either on the display or in the data that was recorded
through the RS interface.
Status and fault signals
The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.
BS = operating status, FS = fault status;
B = Action of the operator
E = The indicated work may only be carried out by an authorised electrician.
K = The indicated work may only be carried out by a service employee of KACO new energy GmbH.
Status Display
Explanation Action
OS 1 Waiting for feed-in Self-test: The grid parameters and
generator voltage are being checked.
- -
OS 2 Generator voltage
too low
Insucient generator voltage and
power,
status before the transition to night
shutdown
- -
OS 8 Self-test
Checks the shutdown of the power
electronics as well as the grid relay
before feed-in mode.
- -
FS 10 Temperature in
unit too high
In case of overheating, the inverter
switches o. Possible causes:
Ambient temperature too high.
Fans covered.
Inverter defective.
" Cool o the area
around the inverter.
" Uncover the fans.
" Notify your
authorised
electrician.
B
B
E
OS 11 Measured values Power limitation: If the generator power is too high, the inverter limits
itself to the maximum power (e.g. around noon if the generator capacity
is too large).
Table 3: Operating status and fault messages on the display