Technical Data
Battery unit extension - Panasonic / Sanyo for Powador-gridsave Page 
4 Technical Data
Electrical data
Battery voltage [V] 48
Number of battery modules 1 2 3 4 5
Nominal capacity [kWh] 1.35 2.70 4.05 5.40 6.75
Max. charge or discharge output [kWh] 0.70 1.40 2.10 2.80 3.50
Cycles 4000 (at 90% discharge depth)
Service life 15 years
Table 3: Electrical data
Mechanical data
Ambient temperature for operation [°C] +5 to +40
Ambient temperature for storage [°C]
-20 … +20 (1 year) … +40 (3
months)
Humidity [%] <95 (non-condensing)
Cooling Forced cooling, temp. regulated
Temperature monitoring
Individual monitoring of
components with shutdown in the
event of excess temperature
Maximum installation elevation (m
above mean sea level]
2000
Protection class IP20
Housing form 19" plug-in module, 2HU
H x W x D [mm] BMS 43x480x475
H x W x D [mm] battery/unit 79x480x400
Weight of BMS [kg] 2.5
Weight per battery/unit [kg] 19
Table 4: Mechanical data